The Fluke 1587 FC combines a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
The Fluke 1587 FC Insulation Multimeter adds four powerful new diagnostic functions through the Fluke Connect® Measurements app:
• PI/DAR timed ratio tests with TrendIt™ graphs identifies moisture and contaminated insulation problems faster
• Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time
• Temperature Compensation through app for establishing accurate baselines and relevant historical comparisons
• Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect® Assets (sold separately)
** THIS PRODUCT COMES WITH A FREE GIFT - an Extech DV23 voltage detector pen, valued at $29 **
QUICK STATS
FEATURES
* PI/DAR timed ratio tests
* Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
* VFD low-pass filter for accurate motor drive measurements
* Auto-discharge of capacitive voltage for added user protection
* Insulation test (0.01 MΩ to 2 GΩ)
* Insulation test voltages (50 V, 100 V, 250 V, 500 V, 1000 V) for many applications
* AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
* Capacitance, diode test, temperature, Min/Max, frequency (Hz)
* Auto power off to save battery power
* CAT III 1000 V, CAT IV 600 V measurement category
* Large display with backlight
* Rugged, utility hard case allows you to bring everything you need for the job
* Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient hands free operation
* Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase
INCLUDED ACCESSORIES
* Hard case
* Remote probe
* Test leads
* Alligator clips
* K-type thermocouple
* User documentation
SPECIFICATIONS
Electrical Specifications | ||
AC voltage measurement | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
¹ 1 kHz bandwidth | ||
Low-Pass Filter Voltage | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
DC Voltage Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
6.000 V dc | 0.001 V | ±(0.09% + 2) |
60.00 V dc | 0.01 V | ±(0.09% + 2) |
600.0 V dc | 0.1 V | ±(0.09% + 2) |
1000 V dc | 1 V | ±(0.09% + 2) |
Input impedance | 10 MΩ (nominal), <100 pF | |
Normal mode rejection ratio | >60 dB @ 50 Hz or 60 Hz | |
Common mode rejection ratio | >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance) | |
Accuracies apply to ± 100% of range | ||
DC Millivolts Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
600.0 mVdc | 0.1 mV | ±(0.1% + 1) |
DC and AC Current Measurement | ||
AC 45 Hz to 1000 Hz | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
DC | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Overload | 600 mA for 2 minutes maximum | |
Fuse protection for mA input | 0.44 mA, 1000 V, IR 10 kA | |
AC conversion | Inputs are ac-coupled and calibrated to the rms value of sine wave input | |
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3. | ||
¹ 1 kHz bandwidth | ||
Ohms Measurement | ||
Range | Resolution | Accuracy +(% of Rdg+Counts)¹ |
600.0 Ω | 0.1 Ω | ±(0.9% + 2) |
6.000 kΩ | 0.001 kΩ | ±(0.9% + 2) |
60.00 kΩ | 0.01 kΩ | ±(0.9% + 2) |
600.0 kΩ | 0.1 KΩ | ±(0.9% + 2) |
6.000 MΩ | 0.001 MΩ | ±(0.9% + 2) |
50.0 MΩ ² | 0.01 MΩ | ±(1.5% + 3) |
Overload protection | 1000 V rms or dc | |
Open circuit test voltage | <8.0 V dc | |
Short circuit current | <1.1 mA | |
¹ Accuracies apply from 0% to 100% of range ² Up to 80% relative humidity |
||
Diode Test | ||
Diode test indication | Display voltage drop: 0.6 V at1.0 mA nominal test current: | |
Accuracy | ±(2% + 3) | |
Continuity Test | ||
Continuity indication | Continuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω | |
Open circuit voltage | <8.0 V | |
Short circuit current | 1.0 mA typical | |
Overload protection | 1000 V rms | |
Response time | >1 m sec | |
Frequency Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
99.99 Hz | 0.01 Hz | ±(0.1% + 1) |
999.9 Hz | 0.1 Hz | ±(0.1% + 1) |
9.999 kHz | 0.001 kHz | ±(0.1% + 1) |
99.99 kHz | 0.01 kHz | ±(0.1% + 1) |
Frequency Counter Sensitivity | ||
600.0 mV ac | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 mV |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 150.0 mV | |
DC Trigger Levels¹ to 20 kHz² | NA | |
6.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 1.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 1.5 V | |
DC Trigger Levels¹ to 20 kHz² | -400.0 mV and 2.5 V | |
60.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 10.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 36.0 V | |
DC Trigger Levels¹ to 20 kHz² | 1.2 V and 4.0 V | |
600.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
1000.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 300.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy ² Usable to 100 kHz with full scale input |
||
Capacitance | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
1000 nF | 1 nF | ±(1.2% + 2) |
10.00 μF | 0.01 μF | ±(1.2% + 2) |
100.0 μF | 0.1 μF | ±(1.2% ±90 counts) |
9999 μF | 1 μF | ±(1.2% ±90 counts) |
Temperature Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts)¹ |
-40 ° C to 537 ° C | 0.1 °C | ±(1% + 10 counts) |
-40 ° F to 998 ° F | 0.1 °F | ±(1% + 18 counts) |
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument | ||
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 2 GΩ | |
Test voltages | 50, 100, 250, 500, 1000 V | |
Test voltage accuracy | +20%, -0% | |
Short-circuit test current | 1 mA nominal | |
Auto discharge | Discharge time <0.5 second for C = 1 μF or less | |
Live circuit detection | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 μF load | |
Output Voltage | ||
50 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 50.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
100 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 60.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 60 to 100 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
250 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 250 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
500 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 500 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
1000 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 600 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 0.6 to 2.0 GΩ | |
Resolution | 100 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(10% + 3 counts) | |
General Specifications | ||
Maximum voltage applied to any terminal and common | 1000 V | |
Storage temperature | -40 °C to 60 °C (-40 °F to 140 °F) | |
Operating temperature | -20 °C to 55 °C (-4 °F to 131 °F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F) | |
Relative humidity | Noncondensing | |
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F) | ||
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F) | ||
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Radio frequency communication | 2.4 GHz ISM Band | |
Radio frequency certification | FCC: T68-FBLE, IC: 6627A-FBLE | |
Electromagnetic Compatibility | ||
International | IEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A | |
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | ||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | ||
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected. | ||
Korea (KCC) | Class A Equipment (Industrial Broadcasting & Communication Equipment) | |
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | ||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | |
Enclosure protection | IEC 60529: IP40 (non-operating) | |
Safety | ||
IEC 61010-1 | Pollution Degree 2 | |
IEC 61010-2-033 | CAT IV 600 V / CAT III 1000 V | |
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | |
Battery life | Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
Altitude | Operating | 2000 m |
Storage | 12,000 m | |
Over-range capability | 110% of range except for capacitance which is 100% | |
Frequency overload protection | <107 V Hz | |
Fuse protection for mA input | 0.44A, 1000 V, IR 10 kA |
DATA SHEET Click here to view in pdf format
We know you want your order FAST, and so we make sure you receive it as quickly as possible.
If your order is in stock, it will ship by the following business day. Shipping is generally 2 - 5 business days (allow 1 or 2 extra days if you're in NT, WA, or a remote location).
And of course we want the ordering process to be as simple as possible for you, so rather than offering tiered shipping rates, we offer FREE SHIPPING AUSTRALIA WIDE on all orders.
If you have any questions about the shipment of your order, feel free to contact us at support@deltapro.com.au
******
Order Confirmation:
As soon as you place your order, you will receive an order confirmation email. This means that we have received your order in our system and pre-authorised your credit card for the purchase. As soon as we receive your order, we automatically reach out to our suppliers to confirm that your item is in stock and available for immediate shipment.
If your item is on backorder (which can increase shipping times up to 4 weeks), we will reach out to you via phone or email before confirming your order.
Shipping Times:
If your order is in stock, it will ship by the following business day. Please allow 2 - 5 business days for shipping (allow 1 or 2 extra days if you're in NT, WA, or a remote location).
Once your item has been shipped you will be emailed a consignment number so you can track your order.
30 Day Guarantee:
If your order arrives and you realise that it's not the right piece of equipment for you, then you are welcome to return it within 30 days of your purchase.
Note: the product must be in new condition, in the original packaging.
To request a refund or exchange, please email support@deltapro.com.au within 30 days of placing your order. Click here for further information on Exchanges and Returns.
Delta Pro are committed to helping you find the right piece of equipment, with the right specifications.
Whether you're looking for a multimeter, clamp meter, leakage tester, insulation tester, thermal imager, or other specialty meter, we have what you need.
And in the unlikely event that we don't, we can most likely source it for you!
We've teamed up with some great delivery drivers to make sure you receive your order as quickly as possible. We know you want your order fast, and we do everything we can to make sure that happens.
Our founder Steve is an electrician himself, and he says there's nothing worse than having dodgy tools and equipment in your toolbox. (We in the office however feel confident there are in fact things much MUCH worse. Like you know, being chased by a crazy, angry bear; or being a hit by speeding bus; or being zapped by 240 volts of electricity while standing bare foot in a puddle... But you know, he's the boss, so we'll go with what he says). Which is why he has made sure that every brand and model stocked in our store is a brand with a solid reputation for quality products.
Shop risk free, and be confident in your choice! If you're not 100% sure you've ordered the best piece of equipment for your needs (although this is unlikely, particularly as you have our easy-to-use search filtering system and Steve's help if you need it!), then you're welcome to return any of our items within 30 days, for a full refund.
(See our Returns Policy for more info).
Delta Pro are authorised dealers for all our brands, which means you get the full manufacturer's warranty on all products. This is a minimum of 12 months unless stated otherwise based on the product.
That's right, Steve has been using multimeters and clamp meters since he was 15 years old. He's got personal experience using a large range of different products, and is pretty well versed on all the different features and functions and what they mean. If you're not sure exactly what you're after, or if you have questions on any of the products, feel free to get in touch. Steve is always happy to chat. Call us on 1300 678 180, email us at info@deltapro.com.au or use the live chat!
Look at what our customers are saying -
"I wanted to get a multimeter for my son, but had no idea where to start. Your home and hobbyist collection really helped." Bob W, NSW
Still not convinced? Find out more More about us and meet Steve in a slightly awkward video (hey, he's an electrician, not movie star!).
And, at the risk of repeating ourselves... did we mention expert advice and support?
If you'd like assistance finding the best multimeter or clamp meter for you, then you're in the right place! Simply click on the image below, answer a couple questions about how and where you're planning on using your new meter, and we'll do the research for you. Then you only need to keep an eye out in your emails for our suggestions.
Confused?
Overwhelmed?
It’s one thing to know what basic functions you require of a multimeter - Voltage, Current, Resistance, Capacitance, Temperature etc. It’s another thing to nut through all the specifications and understand exactly what your multimeter is capable of.
A lot of the time you only need to know the course parameters of each measurement, e.g. up to 1000A current, 600V voltage, 1 mega-ohm resistance etc. But sometimes, particularly in industrial applications, you need to know how your multimeter performs a particular test, how accurate the displayed results are, and whether or not the multimeter will be safe and reliable for the intended application.
This is where terms such as count, range, resolution, basic accuracy, IP rating, CAT rating, True RMS, crest factor and others come into play.
If you are not familiar with these terms and how they relate to multimeter measurement, Steve has put together a series of blogs to explain in laymen’s terms what each mean.